Mike Krzyzewski is really a famous coach of Dream Team. She has coached north america men's basketball team for some time, that's clinched numerous medals for his country. Following Londonfl jerseys supplyn Olympic was over, Krzyzewski told The Associated Press that this game will be his final one as national coach, a job he's held for seven years. He had left open the possibility of swomen nfl jerseystaying with the team beyond the London Games, when practice on Saturday said these will be his last Olympics.When asked if he was sure, Krzyzewski didn't hesitate before again saying, "yecheap nfl jerseys wholesales," this will be his last game "If we could win it, then it might be three major championships in a row, i always do not know when that has been done because we haven't usually won http://govoriotkrito.bg/libs/nflcn08.htmthe globe championships," Krzyzewski said. "It becomes an enormous thing for the program." Whatever, he's an awesome coach. His achievement are going to be remembered by the country.cheap nfl jerseys

KYN28A-12(GZS1)户内金属铠装中置移开式开关柜

更新:2013/9/27 15:44:24      点击:
  • 产品品牌   
  • 产品型号   KYN28A-12(GZS1)
  • 产品描述

    KYN28A-12(GZS1)户内金属铠装中置移开式开关柜,是上海人民电气有限公司 http://www.shamandq.com 为您提供的关于KYN28A-12(GZS1)户内金属铠装中置移开式开...

产品介绍

产品简介:

   KYN28A-12型(GZS1)户内金属铠装中置移开式开关设备系三相交流50Hz的户内成套配电装置,用于接受和分配3-12KV的网络电能并对电路实行控制保护及监测。本产品继电器小室面板上可安装各类型的微机型综合继电保护装置,并可实现系统的智能化控制,具有遥控、遥测、遥信及遥调功能,通过带有通信接口的CAN总线控制现场网络。并具有防止误操作断路器、防止带负荷推拉收车、防止带电关合接地开关、防止接地开关在接地位置送电和防止误入带电间隔,即简称的“五防”功能。该柜既能配用VSI(即ZN63),ZN12V真空断路器,也可配置进口的VD4真空断路器与VC系列真空接触器。

型号及含义:

使用环境条件:

1.周围空气温度:上限40℃下限一般地区-10℃。

2.海拔:1000m.

3.相对温度:日平均值不大于95%,月平均值不大于90%。

  水蒸气压力:日平均值不大于2.2KPa,月平均值不大于1.8KPa。

  当温度骤降时可能出现凝露,伴随污秽,本产品适用于以下比正常条件更严酷的两种环境条件:

  a.凝露不频繁(每月平均不超过两次)有轻度污秽。

   b.一般不出现凝露(每年平均不超过两次)有较严重污秽。

4.没有火灾、爆炸危险及严重污秽足以腐蚀金属和破坏绝缘的气体等恶劣场所。

5.没有剧烈震动、颠簸及垂直倾斜度不超过8°的场所。

注:

1.允许在-30℃时储运。

2.当海拔超过1000m的地区,按JB/Z102《高压电器使用海拔地区的技术要求》处理,当海拔不超过2000m时,低压辅助设备不需要采取任何措施。

3.当实际使用条件与上述不同时,应由用户和制造厂双方协商。

 

符合标准:

产品符合下列标准:

1.IEC-298

2.GB3906

3.DL/T404

4.GB/T11022

开关柜的特点:

   开关柜由固定的柜体和可抽出部件两大部分组成,开关柜柜体的外壳和各功能单元的隔板均采用敷铝锌钢板栓接而成。开关柜外壳防护等级达IP4X,各隔室间隔板及断路器室门打开时的防护等级为IPX2.

   KYN28A-12型开关柜可配用VS1、ZN12V型真空断路器手车和VD4真空断路器手车,及ABB公司生产的VC型真空接触器,开关柜可安装成双重柜并列,即安装成背靠背排列。开关柜的安装与高度可在正面进行,所以开关柜可以靠墙安装,靠墙安装的最大优点可节省占地面积。另外开关柜又可不靠墙安装,即双面维护型,二者内部结构布置是不一致的,其优点是维护方便。开关柜技术参数

序号 名称 单位 数 据
1 额定绝缘水平 额定电压 KV 3.6 7.2 12
1min工频耐压 KV 24 32 42
2 雷电冲击耐压(全波) KV 40 60 75
3 额定频率 Hz 50
4 额定电流 A 630、1250、1600、2000、2500、3150
5 4S短时耐受电流 KA 20、25、31、31.5、40、50
6 额定峰值耐受电流 KV 50、63、80、100、125
7 防护等级   外壳IPX4,各隔室间隔板为IP2X
CRVS1真空断路器技术参数
序号 名 称 单位 VS1、ZN12V VD4
1 额定绝缘水平 额定电压 KV 12
1min工频耐压 KV 42
2 雷电冲击耐压(全波) KV 75
3 额定频率 Hz 50
4 额定电流 A 630、1250、1600、2000、2500、3150
5 额定短路开断电流 KA 16、20、31.5、40、50
6 4S短时耐受电流 KV 16、20、31.5、40、50
7 峰值耐受电流   40、50、63、80、100、125
8 额定操作顺序   分-0.3S-合分180S-合分
9 当额定短路开断电流≥40KA时顺序   分-180S合分-180S-合分
10 合闸顺序   ≤70 ≤60
11 分闸顺序   ≤50 ≤45
12 燃弧时间   ≤15 ≤15
13 开断时间   ≤65 ≤60

高 度:2300mm

宽 度:1.分支母线额定电流1600A及以下,短路开断电流为31.5KA时,为800mm

2.分支母线额定电流1600A以上时,为1000mm。

深 度:1.电缆进出线—1500mm

2.架空进出线—1660mm

开关柜外形尺寸图:

A手车

手车骨架系用薄钢板经CNC机床加工后经铆、焊而成。根据用途,手车可分为断路器手车、电压互感器手车、隔离手车、计量手车等等。相同规格的手车能方便互换。。手车在柜内有隔离位置、试验位置和工作位置,每一位置均设有定位装置,以保证手车处于以上位置时不能随便移动、而移动手车时必须要解除联锁。机械联锁安全、可靠、灵活。

B母线室

母线从一个开关柜引至另一开关柜,通过分支母线和静触头盒固定。扁平的分支母线通过螺栓连接于静触头盒和主母线,不需要任何其他的线夹或绝缘子联接。当用户和工程特殊需要时,母线排上的联接螺栓可用绝缘和端帽封装。在母线穿越开关柜隔板时,用母线套管固定。如果出现内部故障电弧,能限制事故蔓延到邻柜,并能保障母线的机械强度。

C电缆室

电缆室内可安装电流互感器、接地开关、避雷器及电缆、并在其底部配制开缝的可卸铝板;以确保现场的施工方便。

D继电器仪表室

继电器仪表室用于安装各种继电器、仪表、信号指示、操作开关等元器件。此外可根据用户要求在仪表室顶部增加小母线室,可敷设十六路控制小线。

泄压装置

在手车室、母线室、电缆室的上方设有泄压装置,当断路器或主母线,电缆室内发生内部故障电弧时,伴随电弧的出现,开关柜内部气压上升,达到一定的压力后,顶部装置的压力释放金属板将自动打开,释放压力和排泄气体,以确保操作人员和开关柜安全。

锁扣结构

中门与柜体之间的联接采用锁扣结构,并配以提升机构,使中门开启更为方便,当中门处于关闭状态时,其与柜体的联接强度更好,增强了有效抗击内部燃弧故障的能力。

产品图样

概述:

VS1真空断路器为当代国内自行研制的较先进的产品,其外形及操作原理与VD4相近。

VS1型真空断路器采用封闭绝缘形式,主绝缘筒加内外裙边,其爬电比距都达到DL标准要求。

VD4真空断路器及手车为ABB公司的产品,时目前国际最为先进的产品,该断路器与柜体采用的时中置抽出式,这样即便于操作、观察,又便于断路器的退出、转运、维修。由于VD4真空断路器的特殊设计,从而确保了相同规格手车的互换。断路器在柜内移动采用的是丝杠推进机构,使断路器在进出时非常轻松可靠。

防止误操作联锁装置:

开关柜具有可靠的联锁装置,为操作人员与设备提供可靠的安全性与保护。其作用如下:

1.当接地开关在分闸位置时,手车才能从试验位置移至工作位置。

2.断路器手车已充分咬合在试验或工作位置时,才能操作。

3.手车在工作位置时,二次插头被锁定不能拔除。

4.接地开关关合时,手车不能从试验位置移至工作位置。

5.接地开关仅在手车处于试验位置或隔离位置时才能操作。

本开关柜还可以在接地开关操作机构上加装电磁铁锁定机构以提高可靠性,防止高压电缆线带电时,误合接地开关。其订货可按用户的需求选择。

二次插头与手车的位置联锁:

开关柜上的二次线与手车的二次线的联络是通过手动二次插头来实现的。二次插头的动触头通过一个尼龙波纹伸缩管与手车相联,二次静触头座装在开关柜手车隔室的右上方。手车只有在试验位置时,才能插入和解除二次插头,手车处于工作位置时由于机构联锁作用,二次插头被锁定,不能解除。

在电缆室内单独设立有8X40mm的接地铜排,此排能贯穿相邻各柜,并与柜体良好接触,此接地排供直接接地之元器件使用,同时由于整个柜体用敷铝锌板相拼联,这样使整个柜体都处在良好接地状态之中,确保运行操作人员触及柜体安全。

运输与存放:

开关柜在运输与存放过程中注意以下几点:

1.不许倾翻、倒置和遭受剧烈震动、防止靠近火源。

2.应防止淋雨以免产品受潮。

3.不得随意拆卸产品及零部件。

更多产品